High Performance PID Temperature Process Control
The TK high performance PID temperature Process Control feature high-speed sampling cycle rate of 50 ms with ±0.3% display-accuracy. The Process Control offer high precision temperature control with features such as simultaneous heating and cooling control and automatic/manual control options. The all-purpose temperature Process Control are available in various sizes and input/output options, for stable and precise temperature control of any required application.
TECHNICAL SPECIFICATIONS
Display method: 4-digit 7-segment LED
Control method: ON/OFF control, P, PI, PD, PID control
Size: W48 X H48 mm (1/16 DIN)
Input specification:
– Thermocouple: K(CA), J(IC), E(CR), T(CC), B(PR), R(PR), S(PR), N(NN), C(TT), G(TT), L(IC), U(CC), Platinel II
– RTD: DPt100?, DPt50?, JPt100?, Cu100?, Cu50?, Nikel 120?
– Analog: 0-100mV, 0-5V, 1-5V, 0-10V
– 0-20mA, 4-20mA
Sampling cycle: 50ms
Control output 1: SSR drive(11VDC ) [ON/OFF, phase, cycle]
Option input: CT, Digital(DI-1)
Option output: Alarm 1, RS485 comm.
Power supply: 100-240VAC~ 50/60Hz
Protection structure: IP65(front panel)
Display accuracy_RTD:
– At room temperature(23?±5?):(PV ±0.3% or ±1?, select the higher one) ±1-digit
– Out of room temperature:(PV ±0.5% or ±2?, select the higher one) ±1-digit
Display accuracy_Thermocouple:
– At room temperature(23?±5?):(PV ±0.3% or ±1?, select the higher one) ±1-digit
– Out of room temperature:(PV ±0.5% or ±2?, select the higher one) ±1-digit
Display accuracy_Analog :
– At room temperature(23?±5?): ±0.3% F.S. ±1-digit
– Out of range of room temperature: ±0.5?% F.S. ±1-digit
Display accuracy_CT input: ±5% F.S. ±1-digit
Hysteresis(adjustable sensitivity): RTD/Thermocouples: 1 to 100?/?(0.1 to 100.0?/?) variable Analog: 1 to 100-digit
Proportional band: 0.1 to 999.9?/?(0.1 to 999.9%)
Integral time: 0 to 9999 sec
Derivative time: 0 to 9999 sec
Control period: Relay output, SSR drive output: 0.1 to 120.0 sec Current output or SSR drive output selectable: 1.0 to 120.0 sec
Manual reset: 0.0 to 100.0%
Environment_Ambient temperature: -10 to 50?, storage: -20 to 60?
Environment_Ambient humidity : 35 to 85% RH, storage: 35 to 85% RH
Insulation type: Double insulation or reinforced insulation(mark: , dielectric strength between the measuring input part and the power part: 2kV)
Reviews