Temperature/Humidity Transducers
The THD temperature/humidity transducers have built-in temperature and humidity sensors and are capable of various outputs including DC 4-20 mA, 1-5 VDC, RS485 communication. The temperature sensors have a range of -19.9 to 60.0°C and the humidity sensors have a range of 0.0 to 99.9% RH. The THD is available in room type, duct mount type, and wall mount types.
TECHNICAL SPECIFICATIONS
Display method: Non-display
Measured range_Temperature:-19.9~60.0?
Measured range_Humidity: 0.0 to 99.9%RH(recommended: 0.0 to 90.0%)
Output_Temperature:Current output(DC4-20mA)
Output_Humidity:Current output(DC4-20mA)
Sampling cycle:500ms
Power supply:24VDC
Protection structure:IP10
Accuracy_Temperature:±1.0?(at room temperature)
Accuracy_Humidity:±3%RH(30 to 70%RH, at room temp.), ±4%RH(10 to 90%RH)
Resolution:1/1000
Environment_Ambient temperature:-20 to 60?, storage: -20 to 60?