The T 16 transformer is a shell-type double outlet ignition transformer. The secondary windings are centre-earthed. The insulators are manufactured when casting the coils.
APPLICATION
The T16 series transformers are suitable for burner with or wothout a cover and firing any kind of fuel for which the burner is designed. The distance between the electrode points must be such to ensure ignition occurs with the minimum input voltage value.
TECHNICAL SPECIFICATIONS
Primary voltage: 220 V
Intermittence on 3 minutes: 33 %
Frequency: 50 Hz
Secondary voltage: 2x 5000V
Primary current: 1.1 A
Secondary current: 20 mA
Power consumption: 240 VA
Feed cable: 55 cm
Casing: Metallic covers
Insulator: Epoxy-Resin
H.T. terminals: 4 mm dia. Rajah or self-threading